Experts in PAT Testers & Equipment
Order & Advice Line 01642 987976
Free Bundle

Kewtech EZYPAT-PLUS PAT Tester –Battery Operated

SKU: EZYPAT-PLUS
Over 3 In Stock
Reward Points: 790 [?]

  • Optimised for testing Class I and Class II appliances with electronic on/off switches

  • Can also be used to test extension leads

  • Display changes colour to indicated PASS (green) or FAIL (red)

-+
£695.00
Save £300.00
£395.00
£474.00 (Inc. VAT)

Login / Sign Up for Member Discount.
Why do I need a calibration?

Found it Cheaper? Found it Cheaper? Price Match
Need Help? Need Help? Contact Us

Kewtech EZYPAT-PLUS PAT Tester –Battery Operated

Click to enlarge

Select a Free PAT Label Bundle

  • PAT Label Pack - 1000 x Passed, 250 x Failed & 500 x Cable Wrap Labels
    FREE   £36.46
  • Description

Kewtech EZYPAT-PLUS PAT Tester –Battery Operated Details

The Kewtech EZYPAT-PLUS PAT Tester is the intermediate model in Kewtech’s range of EZYPAT/ SMARTPAT PAT Testers. For more information regarding this range please see the comparison table detailed under the ‘Technical Specifications’.

The Kewtech EZYPAT-PLUS PAT Tester is a portable, ergonomic, lightweight PAT tester ideal for examining Class I and Class II appliances as well as extension leads. It is battery operated and can perform up to approximately 1400 tests before its batteries begin to expire.

The EZYPAT-PLUS’ easy-to-read, large, backlit display turns green when a test is passed and red when one is failed. This clear indication adds to the Kewtech EZYPAT-PLUS PAT Tester’s practicality and efficiency, as does its clearly labelled function keys which allow the user to run automatic test sequences tailored to Class I or Class II appliances or extension leads.

Like its sister product, the EZYPAT, available here, the Kewtech EZYPAT-PLUS PAT Tester can perform the following tests:

  • 200mA earth continuity tests (IT safe)
  • Appliance status pre-check (can be used to check whether the appliance under investigation is on or off)
  • Quick continuity check (1 second)
  • 5-second continuity check
  • 250V DC insulation tests (IT safe)
  • 500V DC insulation tests
  • Substitute leakage tests (with selectable parameters)
  • Extension lead tests

Like the EZYPAT, this PAT tester is IT safe as a result of its capacity for low current earth continuity tests and 250V DC insulation tests. Similarly, it also features a Test Lead Nulling function for accuracy. However; unlike the Kewtech EZYPAT, this model can perform leakage tests at 110V and 230V making it suitable for testing appliances that need to be powered on in order to be tested fully, i.e. appliances like computers and TVs which feature electronic on/off switches.

The Kewtech EZYPAT-PLUS PAT Tester is supplied with an EZYLEAD extension Lead Adapter; EZYEARTH Earth Continuity Test Lead with Probe and Crocodile Clip, and an EZYMAIN Mains Lead. These accessories ensure that the user can easily tailor the Kewtech EZYPAT-PLUS to perform the necessary tests.  

These accessories combined with the Kewtech EZYPAT-PLUS PAT Tester’s multitudinous measurement features, and ergonomic, easy-to-use design make it a practical and versatile PAT tester.

Kewtech EZYPAT-PLUS PAT Tester –Battery Operated Key Features

  • Battery operated, easy-to-use, non-downloading PAT tester
  • Optimised for testing Class I and Class II appliances and extension leads
  • Ideal for testing appliances which need to be powered on in order to test fully (such as computers and TVs)
  • Ergonomic and lightweight
  • Can perform up to 1400 tests before the batteries begin to expire
  • Display turns green when a test is passed
  • Display turns red when a test is failed
  • Labelled function keys allow the user perform automatic test sequences tailored for Class I or Class II appliances or extension leads
  • Includes all tests and features present on the EZYPAT
  • 200mA earth continuity tests (IT safe)
  • Appliance status pre-check (can be used to check whether the appliance under investigation is on or off)
  • Quick continuity check (1 second)
  • 5-second continuity check
  • 250V DC insulation tests (IT safe)
  • 500V DC insulation tests
  • Substitute leakage tests (with selectable parameters)
  • Extension lead tests
  • IT safe
  • Test Lead Null function
  • Unlike the EZYPAT, this PAT tester can perform leakage tests at 110V and 230V
  • EZYLEAD Extension Lead Adapter
  • EZYEARTH Earth Continuity Test Lead with Probe and Crocodile Clip
  • EZYMAIN Mains Lead

What’s Included?

  • Kewtech EZYPAT-PLUS PAT Tester –Battery Operated
  • EZYLEAD Extension Lead Adapter
  • EZYEARTH Earth Continuity Test Lead with Probe and Crocodile Clip
  • EZYMAIN Mains Lead
  • Carry Bag with Strap
  • Quick Start Guide
  • End of Line Calibration Certificate
Questions?Do you have a question about this product? Call our customer service team on 01642 631685.
  • Technical Specs

Kewtech EZYPAT/ SMARTPAT Comparision Table

Specification EZYPAT EZYPAT PLUS SMARTPAT
200mA Continuity Test  X X X
250V Insulation Test X X X
500V Insulation Test X X X
Substitute Leakage Test X X X
Polarity Check X X X
110V Load and Run Test X X
230V Load and Run Test X X
Portable RCD Test X
Compatible with KEWPAT App X
Customisable Test Sequences X

Kewtech EZYPAT PAT Tester – Battery Operated Technical Specifications

Protective Conductor Resistance Test
Measuring Range 0.00 - 20.00 Ω (NULL value inc)*
Over-range Indication > 20.00 Ω
Resolution 0.01Ω
Open-circuit Voltage 5 V ±0.4 V DC
Measuring Current 200 mA DC (nominal value)
Accuracy ±3%rdg ±5dgt

* Resistances exceeding 3 Ω cannot be cancelled by NULL function.

Mains Voltage 
Display Range 30 - 270 V
Hi/Lo Indication

< 30 V: No voltage indication
> 270 V: 270 V

Resolution & Accuracy 1 V ±3%rdg ±5dgt
Insulation
Measuring Range  0.00 - 20.00 MΩ
Over-range Indication > 20.00 MΩ
Resolution 0.01 MΩ
No-load Voltage 250V : 250 V DC +20%, -0%
500V: 500 V DC +20%, -0%
Short-circuit Current 1.5 mA DC or less
Rated Current 250V: 1 -1.2 mA with a load of 0.25 MΩ
500V: 1 to 1.2 mA with a load of 0.5 MΩ
Accuracy ±2%rdg±3dgt
Substitute Leakage 
Measuring Range 0.10 - 12.00 mA rms
Over-range Indication > 12.00 mA
Resolution 0.01mA
Open-circuit Voltage/ Frequency 30 V ±5 V rms / 50 Hz ±5%
Measuring Circuit 1.2 mA AC ±0.5 mA (when measuring 12.00 mA)
Accuracy ±3%rdg±5dgt
Insulation Testy Between L-N
Open-circuit Voltage 4.5 V ±0.5 V DC
Criteria of Judgement

100 kΩ ±20 kΩ or less: LCD shows “<0.10 MΩ” and the measurement is halted.

Run Leakage 
Mains Voltage Range 100 - 253 V / 50 Hz
Measuring Range Load Current: 0.10 - 13.00 A rms
Leakage Current: 0.10 - 20.00 mA rms
Display Range Load Current: 0.00 - 13.00 A
Leakage Current: 0.00 - 20.00 mA
Over-range Indication Load Current: > 13.00 A
Leakage Current: > 20.00 mA
Resolution Load Current: 0.01A
Leakage Current: 0.01mA
Accuracy Load Current: ±10%rdg ±5dgt
Leakage Current: ±3%rdg ±5dvgt
Max. Rating Load Current: 3 kVA max. / 15 sec. cont.
Leakage Current: -
Physical Specifications
Safety 

IEC/EN61010-1 CAT II 300V-instrument
IEC/EN61010-2-030
IEC/EN61010-031 CAT III 600V

EMC EN61326-1, 2-2

Possible number of 
measurements where 
battery voltage is within the 
effective range (measuring 
every 30 sec)

Approx. 1400 times 
(CLI Rpe: 0 Ω, Rins: 1.1 MΩ)

Boxed Weight  1.82Kg
Boxed Dimensions (L x W x D) 261 x 140 x 130mm

Questions?Do you have a question about this product? Call our customer service team on 01642 631685.
  • Reviews

We'd really appreciate it if you'd review this product

No reviews have been found

Write Your Own Review

You're reviewing: Kewtech EZYPAT-PLUS PAT Tester –Battery Operated

How do you rate this product? *

  1 star 2 stars 3 stars 4 stars 5 stars
Quality
Price
Value

1.9