Experts in PAT Testers & Equipment
Order & Advice Line 01642 987976
Free Bundle

Martindale HPAT400 Pass/Fail PAT Tester

SKU: HPAT400
Reward Points: 378 [?]

  • IT-safe, easy-to-use, compact non-downloadable PAT tester

  • Integrated three-phase plug

  • Check Class I and Class II appliances and power leads

-+
£319.00
Save £130.00
£189.00
£226.80 (Inc. VAT)

Login / Sign Up
Why do I need a calibration?

Found it Cheaper? Found it Cheaper? Price Match
Need Help? Need Help? Contact Us

Martindale HPAT400 Pass/Fail PAT Tester - Kit

Click to enlarge
Select your Free Item
  • PAT Handbook + Logbook + 750 Labels (500 Pass & 250 Fail)
    FREE   £55.45
  • 110V Adapter + Logbook + 1,000 Labels (500 Pass, 250 Cord & 250 Fail)
    FREE   £113.97
Description

Martindale HPAT400 Pass/Fail PAT Tester Details

The Martindale HPAT400 Pass/Fail PAT Tester can be used to test Class I and Class II appliances as well as power leads. It includes automatic test sequences for these portable appliances which can be engaged by pressing the corresponding button.

This simple-to-use, non-downloadable PAT tester also includes an integrated three-phase plug and an IT-safe 200mA earth bond test. Further to this, the Martindale HPAT400 Pass/Fail PAT Tester is supplied with an extension lead adapter and an earth bond probe with clip and may be used with OPTIONAL adapters for testing 110V appliances.

This instrument also features helpful connection diagrams printed on its body, ensuring that the user is able to carry out the appropriate tests quickly and accurately. The Martindale HPAT400 Pass/Fail PAT Tester’s compact design also expands its scope-for-use as it is able to conduct tests in a variety of locations, for instance, under desks or at wall-mounted monitors.

Results are viewable via the Martindale HPAT400 Pass/Fail PAT Tester’s backlit display and are communicated using a simple but clear PASS or FAIL indication. Please note that this instrument will not display any values.

The Martindale HPAT400 Pass/Fail PAT Tester is an IT-safe, easy-to-use, compact non-downloadable PAT tester optimised for performing fast and full pass/ fail tests on a multitude of portable electrical appliances.

Martindale HPAT400 Pass/Fail PAT Tester Key Features

  • Test Class I and Class II appliances and power leads
  • Automatic test sequences for the aforementioned appliances
  • Start test sequences by pressing the corresponding button
  • Integrated three-phase plug
  • IT-safe 200mA earth bond test
  • Supplied with an extension lead adapter and earth bond probe with clip
  • Supplied with a Test & Go Carry Case with a pouch for accessories
  • Can be used with OPTIONAL adapters for testing 110V appliances
  • Helpful connection diagrams are printed on the tester’s body
  • The connection diagrams aid the user with performing tests accurately and quickly
  • Compact design
  • Can perform tests in a variety of locations
  • Backlit display
  • Simple and clear PASS/ FAIL indication
  • Does NOT display values
  • An IT-safe, easy-to-use, compact non-downloadable PAT tester
  • Optimised for performing fast and full pass/ fail tests on a multitude of portable electrical appliances

What’s Included?

  • Martindale HPAT400 Pass/Fail PAT Tester
  • Extension Lead Adapter
  • Earth Bond Probe with Clip
  • Test & Go Carry Case
  • 6x AA Alkaline Batteries
Technical Specs
Questions?Do you have a question about this product? Call our customer service team on 01642 631685.

Martindale HPAT400 Pass/Fail PAT Tester Technical Specifications

Earth Continuity 
Test voltage 4V DC (into open circuit)
Test current 200mA DC (into short circuit)
Accuracy ± 0.03Ω
Pass Limits Lead ≤ 0.20 Ω = PASS
Class I ≤ 0.20 Ω = PASS
Insulation 
Fixed voltage >500V DC at 1mA (< 625V DC into open circuit)
Test current 1.5mA (into short circuit)
Accuracy ± 0.1MΩ
Pass limits Lead: ≥ 1.0 MΩ
Class I: ≥ 1.0 MΩ
Class II: ≥ 2.0 MΩ
Fuse Check
Test voltage 4V DC (into open circuit)
Test current 200mA DC (into short circuit)
Pass level >2mA
General 
Overload protection 300V AC/DC
Protection class IP20
Safety Complies to BS EN 61010-1
Temperature Range -10 to 40°C, non-condensing
Batteries 6 x AA alkaline batteries
Battery Life minimum 600 complete tests
Auto Power Down After 10 minutes of inactivity, or when battery low
Dimensions 90 x 210 x 54mm
Weight Approx 700g (including batteries & leads)
ALSO BOUGHT..